SureCross DX70 wireless networks consist of a radio frequency network system built around two devices and configured I/O.
| General | Power:+10 to 30V dc Power consumption:less than 1.4 W @ 24V dc Indicators:Green Power ON LED, Yellow Signal Strength LED Mounting:#10 or M5 (M5 hardware included) M5 fasteners—max. tightening torque:0.56 N/m (5 in/lbf) Case material:polycarbonate Weight:0.26 kg External cable gland:one 1/2—NPT type Cable glands, max. tightening torque:0.56 N/m (5 in/lbf) |
|---|---|
| Radio | Range with standard 2 dB antenna*: 900 MHz models:up to 4.8 km (3 miles)
2.4 GHz models:up to 3.2 km (2 miles)
Frequency:900 MHz models::902 -928 MHz ISM band
2.4 MHz models:2.4 - 2.4835 GHz ISM band
Transmit power:900 MHz models:21 dBm conducted
2.4 GHz models:18 dBm conducted, 20 dBm EIRP max.
Spread spectrum technology:Frequency Hopping Spread Spectrum (FHSS)Antenna connector:ext. reverse polarity SMA - 50 ohms Antenna—max. tightening torque:0.45 N/m (4 in/lbf) Link timeout:8 seconds *Note:The range depends upon the environment and line of site. High-gain antennas are available to increase the range. |
| Inputs | Discrete:four sourcing (or sinking) Rating:3 mA max. current @ 30V dc
Sample rate:62 milliseconds
Report rate:On Change of State
ON condition:greater than 8V (less than 0.7V for sinking)
OFF condition:less than 5V (greater than 2V or Open for sinking)
Analog:two, 0 to 20 mASample rate:62 milliseconds
Report rate:1 second or on Change of State (1% change in value)
Accuracy:0.1% of full scale +0.01% per °C
|
| Outputs | Discrete:four sourcing Rating:100 mA max. current @ 30V dc
ON condition:supply minus 2V
OFF condition:less than 2V
Analog:two, 0 to 20 mAMax. end-to-end Latency*:400 milliseconds
Output state following timeout:programmed by dip switch
*Note:from the sample point and with a good RF signal |
| Environmental | Environmental rating*:IEC IP67; NEMA 6 Operating temperature**:-40 to +85° C (electronics); -20 to +80° C (LCD) Relative humidity:95% (non-condensing) Shock and vibration:IEC IEC 68-2-6 and IEC 68-2-7 Shock:30 g, 11 millisecond half-sine wave, 18 shocks
Vibration:0.5 mm p-p, 10-60 Hz
*Note:Operating the devices at the maximum operating conditions for extended periods can shorten the life of the device. |
| Compliance | 900 MHz models:FCC ID TGUDX80 - This device complies with FCC Part 15, Subpart C, 15.247 2.4 GHz models:FCC ID UE300DX80-2400 - This device complies with FCC Part 15, Subpart C, 15.247. ETSI/EN: In accordance with EN 300 328: V1.7.1 (2006-05) |
| Product Specifications and Modifications Disclaimer | All specifications published in this document are subject to change. Banner reserves the right to modify the specifications of products, prior to their order, without notice. |
Industry solutions, application tips, new products, quick video tutorials, trends.
Subscribe Now »“I’m delighted with Banner’s SureCross wireless system. It gives us comprehensive monitoring and control in previously inaccessible locations. And it’s easy to expand and relocate as needed.”
Banner has more than 2,000 distributors worldwide - ready to help you.