| Output Configuration | Each normally-open output channel is a series connection of contacts from two forced-guided (mechanically linked) relays, K1-K2.
The normally-closed contact 31 -32 is a parallel connection of contacts from K1-K2.
ES-FA-9AA:3 normally-open output channels
ES-FA-11AA:2 normally-open output channels and 1 normally-closed auxiliary output channel
Contacts:AgNi, 5 µm gold plated
Low current rating:
Caution:The 5 µm gold-plated contacts allow the switching of low current/low voltage. To preserve the gold plating on the contacts, do not exceed the following max. values at any time.
Min. voltage:1V ac/dc
Max. voltage:60V
Min. current:5 mA ac/dc
Max. current:300 mA
Min. power:5 mW (5 mVA)
Max. power:7 W (7 VA)
High current rating:If higher loads must be switched through one or more of the contacts, the minimum and maximum values of the contact(s) changes to the following.
Min. voltage:15V ac/dc
Max. voltage:250V ac/dc
Min. current:30 mA ac/dc
Max. current:6 A (ES-FA-9AA) and 7 A (ES-FA-11AA)
Min. power:5 W (5 VA)
Max. power:200 W (1,500 VA)
Mechanical life:50,000,000 operations
Electrical life:
ES-FA-9AA:150,000 operations (typical, @ 200 W (1,500 VA) switched power, resistive load)
ES-FA-11AA:130,000 operations (typical, @ 200 W (1,750 VA) switched power, resistive load)
Note:Transient suppression is recommended when switching inductive loads. Install suppressors across load. Never install suppressors across output contacts.
|