| Supply Voltage and Current | 10 to 30V dc (10% max. ripple) @ less than 50 mA (exclusive of load)
|
| Range | Opposed:60 m
Non-polarized Retroreflective:0.08 to 9 m, range is specified using one model BRT-3 retroreflector
Polarized Retroreflective:0.15 to 6 m, range is specified using one model BRT-3 retroreflector
Diffuse (long range):1.8 m
Diffuse (short range):450 mm
Diffuse (high power):3 m
Convergent:38 or 100 mm, depending on model
Plastic and Glass Fiber Optic:Range varies by sensing mode and fiber optics used
|
| Supply Protection Circuitry | Protected against reverse polarity and transient voltages
|
| Output Configuration | Bipolar:One NPN (current sinking) and one PNP (current sourcing); light operate (LO) or dark operate (DO) selectable
|
| Output Rating | 250 mA max. each output up to 50° C, derated to 150 mA @ 70° C (derate 5 mA per ° C)
OFF-state leakage current:less than 1 µA
Output saturation voltage:less than 1V @ 10 mA and less than 2V @ 250 mA
|
| Output Protection Circuitry | Protected against false pulse on power-up and continuous overload or short circuit of outputs
|
| Output Response Time | Response time is independent of signal strength.
Opposed:2 millisecond ON; 1 milliseconds OFF
All others:2 milliseconds ON/OFF
|
| Delay at Power-up | 100 milliseconds; outputs do not conduct during this time.
|
| Repeatability | Repeatability is independent of signal strength.
Opposed:0.25 milliseconds
All others:0.5 milliseconds
|
| Adjustments | Light-operate/dark-operate select switch and multi-turn sensitivity control on top of sensor, beneath a transparent polycarbonate o-ring sealed cover, allows precise sensitivity setting (turn clockwise to increase gain). Optional logic and logic/display modules have adjustable timing functions.
|
| Indicators | Indicator LEDs are highly visible, located beneath a raised transparent polycarbonate dome on top of the sensor.
Power (Green):LED lights whenever 10 to 30V dc power is applied and flashes to indicate ouput overload or output short circuit
Signal (Red):LED lights whenever the sensor sees its modulated light source and pulses at a rate proportional to the strength of the received light signal
Load (Yellow):LED lights whenever an output is conducting
Optional 7-segment display:LED display lights for signal strength
|
| Construction | Molded reinforced thermoplastic polyester housing, o-ring sealed transparent polycarbonate cover, molded acrylic lenses and stainless-steel hardware. Q45s are designed to meet 1200 psi washdown. The base of cabled models has a 1/2 inch NPS integral internal conduit thread.
|
| Environmental Rating | NEMA 6P; IEC IP67
|
| Connections | PVC-jacketed 4-conductor 2 m or 9 m cables, or 4-pin integral Euro-style QD (Q5), or 4-pin integral Mini-style QD (Q), depending on model. QD cable are ordered separately.
|
| Operating Conditions | Temperature:-40° to +70° C
Relative humidity:90% @ 50° C (non-condensing)
|
| Application Note | Optional logic timing modules are available.
|