| Supply Voltage and Current | 12 to 24V dc (10% max. ripple) @ 90 mA (exclusive of load)
|
| Range | “A” suffix models:
Near limit:150 mm min.
Far limit:1 m max.
“B” suffix models:
Near limit:300 mm min.
Far limit:2 m max.
“-CRFV” suffix models:
Near limit:300 mm min.
Far limit:1.5 m max.
|
| Supply Protection Circuitry | Protected against reverse polarity and transient voltages
|
| Output Configuration | SPST solid-state switch conducts when target is sensed within sensing window; choose NPN (current sinking) or PNP (current sourcing) models
|
| Output Rating | 100 mA max. per sensor
OFF-state leakage current:less than 10 µA
ON-state saturation voltage:less than 1V @ 10 mA; less than 1.5V @ 100 mA
|
| Output Protection | Protected against false pulse on power-up and continuous overload or short-circuit of outputs
|
| Output Response Time | “A” suffix models:48 milliseconds
“B” suffix models:96 millliseconds
|
| Sensing Performance | Specified using a 10 x 10 cm aluminum target @ 25° C under fixed sensing conditions.
Repeatability:±0.25% of measured distance
Minimum window size:10 mm
Hysteresis:2.5 mm
|
| Adjustment | Sensing window limits:TEACH-mode programming of near and far window limits may be set using membrane push buttons on sensor or remotely using TEACH input. Window limits may be programmed separately or together.
|
| Indicators | 4 LED indicators:
In RUN mode:
Green ON steady:power ON, RUN mode
Green flashing:output overloaded
Red flashing:relative received signal strength
Yellow ON steady:output conducting
In PROGRAM mode:
Green OFF:PROGRAM mode
Red flashing:relative received signal strength
Yellow ON steady:ready for first window limit
Yellow flashing:ready for second window limit
Yellow OFF:not teaching this output
|
| Construction | Molded reinforced thermoplastic polyester housing
|
| Environmental Rating | Leakproof design is rated IEC IP67; NEMA 6P
|
| Connections | 5-conductor 2 m or 9 m shielded PVC-jacketed attached cable, or 5-pin Euro-style quick-disconnect fitting. QD cables are ordered separately.
|
| Operating Conditions | Temperature:-20° to +70° C
Relative humidity:100%
|
| Vibration and Mechanical Shock | All models meet Mil. Std. 202F requirements. Method 201A (Vibration: 10 to 60 Hz max. double amplitude 0.06”, maximum acceleration 10G). Also meets IEC 947-5-2 requirements: 30G, 11 milliseconds duration, half-sine wave.
|
| Application Note | Objects passing inside the specified near limit will produce a false response.
|