| General | Power:+10 to 30V dc or 3.6 to 5.5V dc low power option Power consumption:less than 1.4 W @ 24V dc Indicators:Two LED, bicolor Switches:Two push buttons Display:Six character LED Mounting:#10 or M5 (M5 hardware included) M5 fasteners—max. tightening torque:0.56 N/m (5 in/lbf) Case material:polycarbonate Weight:0.26 kg External cable gland:four PG-7 type, One 1/2—NPT type Cable glands, max. tightening torque:0.56 N/m (5 in/lbf) |
|---|---|
| Radio | Range with standard 2 dB antenna*: 900 MHz models:up to 4.8 km (3 miles)
2.4 GHz models:up to 3.2 km (2 miles)
Frequency:900 MHz models::902 -928 MHz ISM band
2.4 MHz models:2.4 - 2.4835 GHz ISM band
Transmit power:900 MHz models:21 dBm conducted
2.4 GHz models:18 dBm conducted, 20 dBm EIRP max.
Spread spectrum technology:Frequency Hopping Spread Spectrum (FHSS)Antenna connector:ext. reverse polarity SMA - 50 ohms Antenna—max. tightening torque:0.45 N/m (4 in/lbf) Link timeout:defined by Gateway *Note:The range depends upon the environment and line of site. High-gain antennas are available to increase the range. |
| Inputs | Analog and discrete models: Discrete inputs:two sinking
Discrete rating:3 mA max. current @ 30V dc
Discrete 1, 2 sample rate:125 milliseconds
Discrete 1, 2 report rate:On change of state
Discrete ON condition:less than 0.7V
Discrete OFF condition:greater than 2V or Open
Analog inputs:0-20 mA
Switched power for analog input 1:defaults SP1: 15V @ 150 mA for 500 milliseconds every 15 minutes
Analog 1 sample rate:15 minutes
Analog 1 report rate:15 minutes
Analog 2 sample rate:1 second
Analog 2 report rate:15 seconds or On Change of State (1% change in value)
Thermocouple models:Discrete inputs:two sinking
Discrete rating:3 mA max. current @ 30V dc
Discrete 1, 2 sample rates:1 second
Discrete 1, 2 report rates:On change of State
Discrete ON condition:less than 0.7V
Discrete OFF condition:greater than 2V or Open |
| Outputs | Analog/discrete and thermocouple models: Discrete outputs:two NMOS sinking
Discrete rating:less than 10 mA max. current @ 30V dc
Discrete update rate:up to 1 per second
Discrete ON condition:less than 0.7V
Discrete OFF condition:open
State following timeout:de-energized (OFF)
|
| Thermocouple | Thermocouple models only: Thermocouple inputs:three
Thermocouple input sample rate:1 second
Thermocouple input report rate:periodic, 16 seconds
Thermistor inputs:one, model number BWA-THERMISTOR-001
Resolution:0.1° C, 24-bit A/D converter
Thermocouple accuracy:0.1%of full scale reading +0.8° C
Thermistor accuracy:0.4° C (10 to 50° C); up to 0.8° C (-40 to +85° C)
|
| Environmental | Environmental rating*:IEC IP67; NEMA 6 Operating temperature**:-40 to +85° C (electronics); -20 to +80° C (LCD) Relative humidity:95% (non-condensing) Shock and vibration:IEC IEC 68-2-6 and IEC 68-2-7 Shock:30 g, 11 millisecond half-sine wave, 18 shocks
Vibration:0.5 mm p-p, 10-60 Hz
*Note 1:Please refer to the SureCross DX80 Quick Start Guide, Banner part number 128185, for installation and waterproofing instructions.*Note 2:Operating the devices at the maximum operating conditions for extended periods can shorten the life of the device. |
| Compliance | 900 MHz models:FCC ID TGUDX80 - This device complies with FCC Part 15, Subpart C, 15.247 2.4 GHz models:FCC ID UE300DX80-2400 - This device complies with FCC Part 15, Subpart C, 15.247. ETSI/EN: In accordance with EN 300 328: V1.7.1 (2006-05) |
| Product Specifications and Modifications Disclaimer | All specifications published in this document are subject to change. Banner reserves the right to modify the specifications of products, prior to their order, without notice. |
Helpful application information, new product updates, answers to frequently asked questions, and more.
Subscribe Now »Browse by model family or type in your model number to find STEP, IGS, DXF, or PDF files for your project.